Free ICC Practice Questions
10 free, exam-style ICC Building Inspector Certification (ICC) practice questions with answers and
explanations. No signup required. Work through them below, then take the
full free ICC practice test to study every exam domain.
Question 1
An inspector is reviewing a garage-to-dwelling separation. The garage wall has 1/2-inch gypsum board on the garage side, and the door between the garage and the hallway is a solid wood door without a self-closing device. What violation exists?
- The gypsum board thickness is insufficient
- The door must be self-closing
- The door must be fire-rated
- Both the gypsum board and the door are violations
Show answer & explanation
Correct answer: B - The door must be self-closing
Question 2
A restaurant with tables and chairs has 3,000 sq ft of net dining area. Using the occupant load factor of 15 net sq ft per person, the calculated occupant load is:
- 100 persons
- 150 persons
- 200 persons
- 300 persons
Show answer & explanation
Correct answer: C - 200 persons
Question 3
A 2×6 bearing stud has a 2-inch diameter hole drilled through it at mid-height. The actual depth of a 2×6 is 5.5 inches. Is this bore compliant?
- Yes, 2 inches is within the 40% limit of 2.2 inches
- No, 2 inches exceeds the 25% notch limit
- Yes, 2 inches is within the 60% bore limit
- No, the hole is too close to the center of the stud
Show answer & explanation
Correct answer: A - Yes, 2 inches is within the 40% limit of 2.2 inches
Question 4
A contractor has drilled a 4-inch hole through a 2×12 floor joist (actual depth 11.25 inches) located at mid-span. The hole is centered on the joist depth. Is this compliant?
- Yes, the hole is within the 1/3 depth limit (3.75 inches)
- No, the hole exceeds the 1/3 depth limit of 3.75 inches
- Yes, holes up to 1/2 the depth are permitted at mid-span
- No, holes are not permitted at mid-span
Show answer & explanation
Correct answer: B - No, the hole exceeds the 1/3 depth limit of 3.75 inches
Question 5
An inspector examines a 2-hour rated fire barrier and finds an unprotected pipe penetration. This is:
- Acceptable if the pipe is steel
- A violation - all penetrations in fire barriers must be protected with listed firestop systems
- Acceptable if the pipe diameter is less than 1 inch
- A violation only if the penetrating item is combustible
Show answer & explanation
Correct answer: B - A violation - all penetrations in fire barriers must be protected with listed firestop systems
Question 6
A rectangular room measures 80 feet by 60 feet. The diagonal distance is 100 feet. Two exits are required. The minimum separation between the exits in a non-sprinklered building is:
- 25 feet
- 33 feet
- 50 feet
- 67 feet
Show answer & explanation
Correct answer: C - 50 feet
Question 7
An inspector measures a stairway and finds riser heights of 7-1/2 inches, 7-3/4 inches, 7-1/2 inches, and 8 inches. The variation between the largest and smallest riser is:
- 1/4 inch - compliant
- 3/8 inch - compliant
- 1/2 inch - NOT compliant
- 3/4 inch - NOT compliant
Show answer & explanation
Correct answer: C - 1/2 inch - NOT compliant
Question 8
An inspector finds that a contractor has used expanding foam sealant (non-listed) to fill a penetration through a 2-hour fire-rated wall. This is:
- Acceptable if the foam is fire-resistant
- Not compliant - penetrations must be protected with a listed through-penetration firestop system
- Acceptable for openings less than 4 inches
- Compliant if the foam expands to fill the entire opening
Show answer & explanation
Correct answer: B - Not compliant - penetrations must be protected with a listed through-penetration firestop system
Question 9
An inspector examines a corridor in a non-sprinklered commercial building and finds that the wall covering material has a flame spread index of 40. Per Table 803.13, corridors require Class A (0-25). This material is:
- Compliant - 40 is close enough to Class A
- Not compliant - the material exceeds the Class A limit of 25
- Compliant - Class B (26-75) is permitted in all corridors
- Not compliant only if the corridor serves more than 30 occupants
Show answer & explanation
Correct answer: B - Not compliant - the material exceeds the Class A limit of 25
Question 10
An inspector measures a bedroom EERO and finds: 24 inches height, 24 inches width, and the sill is 46 inches above the floor. The net clear area is 576 sq in (4.0 sq ft). How many violations exist?
- One - the sill height exceeds 44 inches
- Two - the sill height exceeds 44 inches AND the area is less than 5.7 sq ft
- Three - sill height, area, and width are all violations
- No violations - all dimensions are within limits
Show answer & explanation
Correct answer: B - Two - the sill height exceeds 44 inches AND the area is less than 5.7 sq ft